AHU modulating mixing box

$1,052.82 / EA

HV-188 · MasterFormat 23 40 00 · EA

What’s in this rate

This unit is setting and installing one modulating mixing box section on an air-handling unit. The HVAC technician sets the section, connects the damper linkage share as furnished, and leaves the mixing box ready for controls and startup. The rate is per each AHU modulating mixing box; hinged access doors, economizer, discharge, fan, coil, and filter sections are separate units.

Includes

  • AHU modulating mixing box section (class mid)
  • damper / linkage / fastening share
  • set/install and leave controls-ready
  • small tools

Excludes

  • AHU hinged access door only
  • AHU economizer, discharge, fan, coil, or filter section
  • standalone outdoor-air damper without mixing box
  • controls, BAS, or TAB
  • crane or lift premium
  • ongoing maintenance or after-hours work

Build-up

Labor 2.5 hr × $68.00 wage and burden
$170.00
Material and small tools
$700.10
Direct rate (labor, material, and tools)
$870.10 / EA
Overhead 10% of direct
$87.01
Fee 10% of (direct and overhead)
$95.71
Loaded rate
$1,052.82 / EA

Use this in a private library

Create a free account to keep your own hours, burden, and supplier quotes behind a login. Published rates stay public. Your own hours and quotes stay private.