Inline mixed-flow exhaust fan
$931.82 / EA
HV-175 · MasterFormat 23 34 00 · EA
What’s in this rate
This unit is setting and installing one inline mixed-flow exhaust fan in a prepared duct run. The HVAC technician hangs the fan, connects both duct collars as furnished, and leaves the assembly ready for power, controls, and balance. The rate is per each inline mixed-flow exhaust fan; ceiling cabinet, wall propeller, roof centrifugal, upblast, inline axial, and inline centrifugal fans are separate units.
Includes
- inline mixed-flow exhaust fan (class mid)
- hang and support share
- duct-collar connection allowance
- set/install and leave power-ready
- small tools
Excludes
- ceiling cabinet, wall propeller, roof centrifugal, or upblast fan
- inline axial or inline centrifugal exhaust fan
- electrical power or controls beyond fan leads
- ductwork beyond the fan collars
- crane or lift premium
- ongoing maintenance or after-hours work
Build-up
- Labor 2.75 hr × $68.00 wage and burden
- $187.00
- Material and small tools
- $583.10
- Direct rate (labor, material, and tools)
- $770.10 / EA
- Overhead 10% of direct
- $77.01
- Fee 10% of (direct and overhead)
- $84.71
- Loaded rate
- $931.82 / EA